- 2067 Mangsir (old course) · 4 marks
Star-delta transformer cannot parallel with star-star
Short answer
A star–delta transformer introduces a 30° phase shift between primary and secondary line voltages, while star–star and delta–delta have 0° shift. Paralleling them creates a voltage difference of about 52% of rated voltage across very low impedance, causing a large circulating current that can damage windings.
Justify the statement: It is not possible to operate star delta transformer in parallel with star-star or delta-delta transformer.
Parallel operation requires that the secondary line voltages of the two banks be exactly equal in magnitude and in phase. A star–delta transformer does not meet this condition with a star–star or a delta–delta bank.
Reason: phase displacement
- In a star–star or delta–delta transformer, the secondary line voltage is in phase with the primary line voltage (0° shift).
- In a star–delta (or delta–star) transformer, the secondary line voltage is displaced by 30° from the primary (lagging for Yd1, leading for Dy11).
When the primaries are on the same supply, the secondary line voltages of the two banks differ by 30°.
V (Y-Y secondary)
^
| 30 deg
| / V (Y-D secondary)
| /
+----------------->
The voltage difference across the paralleled terminals is
This is about 52% of the rated secondary voltage. It appears across the very low internal impedances of the two transformers, so a huge circulating current flows, even at no load. The windings overheat and may be damaged, and the load cannot be shared properly.
Also: the voltage ratios differ in form. Star–delta has compared with for star–star, so the turns would have to be redesigned. Even if the magnitudes matched, the 30° displacement cannot be removed by any change of turns ratio.
Hence star–delta can be paralleled only with another star–delta, or with a transformer that has the same phase displacement (the same vector group), such as delta–star of the right group.
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Star-delta starting torque ratio and full-load slip · Electrical Machines, chapter 5
- Parallel transformers and per-unit impedance load sharing · Electrical Machines I, chapter 2
- CT secondary should not be kept open · Electrical Machines, chapter 2
- Load sharing of 50 kVA and 25 kVA transformers in parallel · Electrical Machines I, chapter 2
- Currents and efficiency of 132/11 kV transformer at 5 MW · Electrical Machines I, chapter 2 · asked 3×
- Currents and efficiency of 132/11 kV transformer at 4 MW · Electrical Machines I, chapter 2 · asked 3×
- Delta/star 120 kVA transformer values · Electrical Machine, chapter 2
- 500 kVA delta/star transformer efficiency · Electrical Machine, chapter 2
- CT ratio for 33/6.6 kV star/delta (300:5) · Switchgear and Protection, chapter 7
- CT ratio for 33/6.6 kV star/delta (400/5) · Switchgear and Protection, chapter 7