Short answer

At 25% overload (x=1.25): copper loss = 1.25² × 1800 = 2812.5 W, iron loss = 700 W, output power = 1.25 × 150 × 0.8 = 150 kW, efficiency = 150000/(150000+3512.5) × 100 = 97.71%.

What is capacity of transformer? A 150 kVA single phase transformer has an iron loss of 700 W and a full load copper loss of 1800 W. Calculate the copper loss, iron loss, output power and efficiency of transformer at 0.8 power factor lagging when secondary is 25% overloaded.

Capacity of a transformer is its rated apparent power output (in kVA) at rated voltage and frequency. It is given in kVA, not kW, because the copper loss depends on the current and the core loss on the voltage, both independent of the power factor of the load.

Given: 150 kVA, Pi=700P_i = 700 W, Pcu,fl=1800P_{cu,fl} = 1800 W, pf =0.8= 0.8 lagging, load =125%= 125\% of full load, so x=1.25x = 1.25.

Copper loss at 25% overload

Pcu=x2Pcu,fl=1.252×1800=2812.5 WP_{cu} = x^2P_{cu,fl} = 1.25^2\times1800 = 2812.5\ \text{W}

Iron loss is independent of load: Pi=700P_i = 700 W.

Output power

Pout=x×S×cos⁡ϕ=1.25×150×0.8=150 kWP_{out} = x\times S\times\cos\phi = 1.25\times150\times0.8 = 150\ \text{kW}

Efficiency

Total loss=2812.5+700=3512.5 Wη=150 000150 000+3512.5×100=97.71%\begin{aligned} \text{Total loss} &= 2812.5 + 700 = 3512.5\ \text{W} \\ \eta &= \frac{150\,000}{150\,000 + 3512.5} \times100 = 97.71\% \end{aligned}

Answer: copper loss = 2812.5 W; iron loss = 700 W; output = 150 kW; efficiency = 97.71%