- 2078 Chaitra · 4+2 marks
Receiving end power in ABCD terms and maximum power
Short answer
From V_S = A V_R + B I_R, receiving power is P_R = (|V_S||V_R|/|B|) cos(β−δ) − (|A||V_R|^2/|B|) cos(β−α). Maximum active power occurs when δ = β, giving P_Rmax = |V_S||V_R|/|B| − |A||V_R|^2 cos(β−α)/|B|.
Starting from a suitable point, find the expression of power at the receiving end of a line in terms of sending and receiving end voltages and line ABCD constants. Also, find the expression for maximum active power at the receiving end.
Start from the ABCD relation of a two-port line:
Take as reference and let
Receiving-end current
Receiving-end complex power
Separating real and imaginary parts:
With phase voltages these give power per phase; with line voltages they give total three-phase power.
Maximum receiving-end power
For fixed , and line constants, only can vary. The second term is constant, so is maximum when , i.e.
At this point the reactive power at the receiving end is
which is negative, so the load must supply (leading) reactive power to receive maximum active power.
For a short line (, ):
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- Sending end active power from ABCD, 132/130.5 kV · Power System Analysis I, chapter 6
- Receiving and sending end powers from ABCD, 132/134 kV · Power System Analysis I, chapter 6
- 150 mile, 60 Hz line: ABCD and sending end · Power System Analysis I, chapter 5
- 220 kV line, 200 MW: sending end from ABCD · Power System Analysis I, chapter 6
- Long line sending end voltage derivation · Power System Analysis I, chapter 5
- Receiving end complex power and power circle · Power System Analysis I, chapter 6
- Expression for receiving-end shunt compensation · High Voltage Engineering, chapter 3
- Receiving-end voltage infinite at 1500 km · High Voltage Engineering, chapter 3
- Fault at receiving end of 220 kV lines · Power System Analysis II, chapter 3
- Critical clearing for temporary sending-end fault · Power System Analysis II, chapter 6