- 2072 Magh · 6 marks
Making short-line regulation zero
Short answer
Voltage regulation of a short line is made zero by operating the receiving end at a leading power factor equal to X/|Z| (tan φ = R/X). This is achieved by connecting a shunt capacitor or synchronous condenser to supply the required leading reactive power.
How can the voltage regulation of a short transmission line be made zero? Explain with necessary mathematical derivation.
The voltage regulation of a short line is zero when the receiving-end voltage at full load equals the sending-end voltage, i.e. . This happens only for a suitable leading power factor at the receiving end.
Derivation
Short line: . Take as reference and the current at angle (lagging taken positive):
The quadrature part changes very little, so
For a leading load the angle is negative, so changes sign. Writing from here on for the magnitude of the leading angle:
Condition for zero regulation
Equivalently, the load angle , where is the line impedance angle.
I (leads Vr by phi)
/ Vs (same length as Vr)
/ .
/ . IZ (perpendicular to Vr+Vs bisector)
/ .
O--------------> Vr
How it is achieved in practice
- Connect a shunt capacitor bank or synchronous condenser at the receiving end so that the net receiving-end pf becomes leading.
- Required leading reactive power (approx.): , so capacitor rating .
- If the load is already more leading than this (negative regulation), a shunt reactor is added instead.
Example: , : zero regulation needs leading.
(For an exact value, solve for ; it gives a slightly more leading pf than the approximate formula.)
✓ Answer checked by Claude Opus 5.5 (high effort)
Related questions
- 70 km, 40 MW line: regulation and zero-regulation pf · Power System Analysis I, chapter 6
- Capacitor for zero regulation, 70 km 220 kV line · Power System Analysis I, chapter 6
- 15 km line: regulation and zero-regulation capacitor · Power System Analysis I, chapter 6
- 12 km 33 kV line: losses, zero-regulation capacitor · Power System Analysis I, chapter 6
- 33 kV, 12 MW leading load: efficiency, zero regulation · Power System Analysis I, chapter 6 · asked 2×
- Efficiency at 0.995 leading pf and zero regulation · Power System Analysis I, chapter 6
- Regulation of 1.5 MVA generator and zero-regulation pf · Electric Machines II, chapter 1
- 5 MVA alternator: regulation and pf for zero regulation · Electrical Machines, chapter 6
- Voltage regulation inversely proportional to V² · Transmission and Distribution System Design, chapter 7
- Regulation and zero-regulation power factor of 100 kVA transformer · Electrical Machines I, chapter 2